ADEL SYSTEM - Battery Chargers - “Battery Care” the Charging Philosophy

Battery charger from ADELSYSTEMYet another innovative product offering from ADEL SYSTEM, as a result of the continuing commitment to provide system designers and users with value added, multi-function devices for battery charging and back-up power supply.

After many years of developing problem-free solutions addressing the requirements of standard and specialised applications, ADEL SYSTEM “focusses on battery charging” and allows designers to safely concentrate on the other more strategic issues of their projects.

This is the background that led to the development of the CB Series of battery chargers with an output voltage of 12, 24 and 36 V.
They are extremely compact and cost-effective. Thanks to the CB  range it is possible to keep a single multi-purpose product suited to different input voltages (120V - 230 Vac), all battery types and able to match most current and voltage output requirements on stock.

Switching technology and the Battery Care concept, part of the core know-how at ADEL SYSTEM,  led to the development of this advanced multi-stage battery charging method, completely automatic and suited to meet the most advanced requirements of battery manufacturers.
The Battery Care concept is base on algorithms that implement rapid and automatic charging, battery charge optimisation over time, flat battery recovery and real time diagnostics during installation and operation. Battery faults such as battery sulfatation, elements in short circuit and accidental reverse polarity connection can easily be detected, identified and removed.

Safety and long term reliability mean optimised charge and extended battery life. Conditions which could cause irreversible damage are prevented by continuosly adapting the charging parameters to the charge status of the battery and ambient conditions.

The CB Series meet the highest standards of quality and ensure high reliability, with MTBF values of up to 300.000 hours.

 

Battery Charger Selection Chart

 

 

Battery Charger Features

 One device for alll battery types

One device for all battery types

Completely automatic, the battery chargers in the CB series are micro-processor controlled devices suited to charging most battery types thanks to factory pre-set and selectable charging curves.
They can charge open lead acid, sealed lead acid, Gel and Ni-Cd, Ni-MH batteries. It is possible to change or add other charging curves by connecting the device to a portable PC.

 Multi stage battery charging

Multi-Stage charging - Three charging modes

Automatic multi-stage operation and real time diagnostics, allow fast recharge and recovery of deeply discharged batteries, thereby adding value and reliability to the system hosting the CB device. The type of charging is voltage stabilised and current stabilised (IUoUo).
CB battery chargers feature three charging modes, identified by a flashing code on a LED.

  • Boost (Boost - Bulk) (Blinks 2/sec)
  • Trickle (also known as float or maintenance charging) (Trickle - Float) (Blink 1/Sec.)
  • Recover (Recovery) (Blinks 5/sec.)
 Battery recovery charging

Recovery charging

The automatic multi-stage operation optimises and adapts to the battery status, even when the battery voltage is very low. The CB can recharge batteries even when their voltage is close to zero. It allows the recharge and complete recovery of flat batteries.

 Battery charge level

Setting the maximum battery charging current

The maximum battery charging current can be set from 20% to 100% of the devices rated value.  Not available on LC models.

 Battery diagnostics

Battery and device diagnostics

All CB devices support the user during installation and operation.
An LED flashing sequence code allows the user to discriminate between various possible faults.

LED Diagnosis:

  • 1 flash - Reverse polarity, wrong battery voltage.
  • 2 flashes - Disconnected battery.
  • 3 flashes - Battery element in short circuit.
  • 5 flashes - Battery to be replaced (Internal impedance bad or bad battery cable connection).
 Battery Charger System Diagnostics

Maximum safety and protection

The CB series is designed to provide safe operation and long battery life. The following are standard features:

  • Output protected against short circuit and overload
  • Protection against deep battery discharge
  • Protection against reverse polarity connection
  • High insulation between primary and secondary
  • Detection of batteries with an incorrect voltage rating
  • Protection against the effect of parallel connection with other power sources, e.g. gensets.

All forms of protection have an automatic reset. No thermal fuse to be replaced.

 Battery Charger monitoring signals

 

Monitoring signals

Signal contacts

  • CB chargers indicate battery status and faults via a change-over contact with galvanic isolation.
  • Battery common fault.
  • Unit disconnected from mains.

Visual indication

  • Battery common fault
  • Unit disconnected from mains
  • Charging mode
  • CB deviced self-diagnostic
 Battery Charger Diagnostic Checks

 

Diagnostic checks

  • Check for accidental disconnection of the battery cables - If this occurs the device switches off the power to the battery.
  • Testing the quality of the cable connections - During trickle charge the quality (resistance) of the battery connection is checked every 20 sec. This is to detect if the cable connection has been properly made.
  • Test of battery voltage
  • Appropriate voltage check - to prevent the connection of incorrect battery types.
  • End of charging check - When the battery it is completely charged, the device automatically switches to trickle charge mode.
  • Reverse polarity check - If the battery it is connected with inverted polarity, the devices are automatically protected.
  • Check for elements in short circuit - Thanks to specific algorithms of evaluation, the CBs recognise batteries with elements in short circuit.

 

Battery Charger Selection Chart

ADEL SYSTEM Product Range

Contact us Today

Our Address:
RET Automation House
130 Boeing Road East, Bedfordview,
South Africa, 2007.

Contact Details:
Phone: +27 (0) 11 453 2468
Premicell: 082 201 2209
Email:    This email address is being protected from spambots. You need JavaScript enabled to view it.

Hours of Operation:
Monday to Friday - 8am to 4:30pm

ADEL SYSTEM Product News

adel-system-flex-power-supply-units RET Automation Controls stocks the complete ADEL System FLEX range of rail mount Power Supplies. FLEX power supplies are available with 1, 2 and 3-phase input, up to 600W, and with a continuous current rating ranging up to 25A. They easily supply power...
387

Latest News

Request a Call

We have helped thousands of customers solve their challenging applications, let us help you!
 

QUICK MENU

RET Automation Controls

Customers First
Integrity Always
Quality in Everything
New Solutions – Every Day

 

RET Automation Controls provides market leading solutions to the factory automation and process automation markets in Southern Africa.  Over the last 30 years RET Automation Controls has been privileged to be able to develop relationships with global leaders in the automation industry, creating a portfolio of complementary products to enable the establishment and maintenance of mutually beneficial long term customer relationships.RET Automation Controls has always ensured that it is supplying products for which it can be proud of and which enhance RET’s reputation as a supplier of high quality innovative products and solutions.

S5 Box